Guangzhou Lengtong Refrigeration's Refrigeration Encyclopedia: Why Does the Cold Storage Have Poor Refrigeration Effect?
Release time:
2025-11-03
Guangzhou Lengtong's refrigeration knowledge: Why is the cold storage not cooling? What are the solutions?
Guangzhou Lengtong Refrigeration's Refrigeration Encyclopedia: Why Does the Cold Storage Have Poor Refrigeration Effect?
During the operation of a cold storage, a common misconception is that a lower evaporation temperature leads to a better refrigeration effect. However, in actual operation, when the evaporation temperature of the cold storage is too low, it often results in a poorer refrigeration effect instead. This article briefly analyzes the common reasons for excessively low evaporation temperature and poor refrigeration effect in cold storage for your reference.
Why Does Excessively Low Evaporation Temperature Lead to Poor Refrigeration Effect?
To understand this phenomenon, we need to understand the basic principles of cold storage refrigeration. The cold storage refrigeration system cools by having the refrigerant evaporate and absorb heat in the evaporator. While a lower evaporation temperature might superficially suggest stronger cooling capacity, it actually leads to a reduction in refrigeration capacity. In practical applications, common reasons why excessively low evaporation temperature反而 leads to poor refrigeration effect include the following:
1、Excessive Frost Buildup on Evaporator, Severely Reducing Heat Transfer Efficiency
The surface temperature of the cold storage evaporator is usually below 0°C, and the storage room humidity is relatively high. Moisture in the air easily condenses and freezes (frosts) or even forms ice on the evaporator surface. When the evaporation temperature is too low, frost forms faster and builds up thicker.
Impact Mechanism: Excessive frost layer hinders heat transfer, significantly reducing the heat transfer coefficient of the evaporator and increasing thermal resistance. This prevents the refrigerant from fully absorbing heat in the evaporator, greatly reducing the refrigeration effect.
Solution: Perform regular manual defrosting or electric defrosting. Methods like "shutdown defrosting" (stopping compressor operation, opening the storage door to allow the room temperature to rise, waiting for the frost layer to melt automatically, then restarting) or "flush defrosting" (removing stored goods, rinsing the evaporator coil surface with relatively warm tap water) can be used.
2、Accumulation of Lubricating Oil in Evaporator, Forming Oil Film that Hinders Heat Transfer
During cold storage operation, some lubricating oil can enter the evaporator along with the refrigerant. When the evaporation temperature is too low, the lubricating oil is more likely to form an oil film on the inner wall of the evaporator coils.
Impact Mechanism: The oil film significantly reduces the heat transfer efficiency of the evaporator, decreasing the heat transfer coefficient and increasing thermal resistance. The amount of refrigerant evaporation decreases, leading to lower system evaporation pressure and further worsening the refrigeration effect。
Solution: Perform regular system oil purging and use hot gas defrosting to carry lubricating oil out of the evaporator. It is recommended to check and perform system oil purging every 3-6 months.
3、Expansion Valve Opening Too Small, Insufficient System Refrigerant Flow
The expansion valve is a key component controlling refrigerant flow. When the expansion valve opening is too small, the system refrigerant supply becomes insufficient.
Impact Mechanism: Insufficient refrigerant flow leads to lower evaporation pressure, which correspondingly lowers the evaporation temperature. However, simultaneously, the amount of refrigerant evaporation decreases, the system's cooling capacity drops, and the refrigeration effect反而 becomes worse.
Solution: Check and adjust the expansion valve opening to ensure the refrigerant flow meets system requirements. Adjust the expansion valve opening appropriately based on changes in the storage room load.
4、Compressor Capacity Too Large ("Using a Big Horse to Pull a Small Cart")
Cold storage compressors are typically sized based on the maximum load of the refrigeration system. The maximum load for fruit and vegetable cold storage mainly occurs during the product loading stage, while at other times the load is often less than 50%.
Impact Mechanism: After the loading is complete and the temperature drops to the suitable storage temperature, the system load decreases significantly, but the compressor may still operate at high capacity, creating a "big horse pulling a small cart" scenario. This leads to excessively low evaporation temperature, reduced refrigeration efficiency, and increased energy consumption.
Solution: Reduce the number of operating compressors promptly according to changes in storage room load, or use capacity control devices to reduce the number of working cylinders. Installing an automatic load regulation system that adjusts compressor operation based on actual load is recommended.
5、Insufficient Evaporator Design Capacity
Inadequate consideration during design, or a mismatch between the actual stored products and the design plan, can lead to increased heat load.
Impact Mechanism: For example, a cold storage designed for storing apples is actually used for storing garlic sprouts. Due to the short harvesting period of garlic sprouts, large quantities need to be loaded within a short time, drastically increasing the heat load. To achieve rapid cooling, the system is forced to lower the evaporation temperature, leading to decreased refrigeration efficiency.
Solution: Increase the evaporator surface area or replace it with a higher capacity evaporator. The heat load characteristics of the actual stored products should be fully considered during the cold storage design phase.
6、Insufficient Refrigerant or Refrigerant Leakage
Refrigerant is the core component of cold storage refrigeration. Insufficient refrigerant or leaks lead to decreased refrigeration efficiency.
Impact Mechanism: Insufficient refrigerant causes the system evaporation pressure to drop, lowering the evaporation temperature. Simultaneously, insufficient refrigerant directly reduces the cooling capacity, resulting in a poor refrigeration effect.
Solution: Check for refrigerant leakage points (soapy water can be applied to pipe connections; bubble formation indicates a leak). After repairing the leak, replenish with an appropriate amount of refrigerant. Regularly checking refrigerant pressure and liquid level is recommended
7、Poor Condenser Heat Dissipation, Affecting Overall System Efficiency
Poor condenser heat dissipation leads to high system condensing pressure, affecting the refrigeration effect.
Impact Mechanism: High condensing pressure increases the compressor load, reduces the overall system refrigeration efficiency, and indirectly leads to excessively low evaporation temperature and poor refrigeration effect.
Solution: Regularly clean dust and dirt from the condenser surface to ensure good heat dissipation. Check if the condenser fan is working properly, and clean or replace it if necessary.
An excessively low evaporation temperature leading to poor refrigeration effect in cold storage is a typical case of "going beyond the limit is as bad as falling short." The refrigeration effect does not solely depend on the temperature level but is closely related to the overall balance of the system. By understanding the reasons above, reasonably adjusting cold storage operating parameters, and maintaining equipment regularly, one can effectively avoid the problem of poor refrigeration effect caused by excessively low evaporation temperature, improve cold storage operating efficiency, reduce energy consumption, and extend equipment service life.
The core goal of cold storage refrigeration is to "maintain a stable refrigeration effect at a reasonable temperature," not merely to pursue extremely low temperatures. Scientific temperature control and system maintenance are the keys to achieving efficient refrigeration.
Latest News
Guangdong Lengtong is a professional refrigeration equipment manufacturer in Guangdong China. 20+ years factory, supply condensing units, cold storage, solar cold room, water chillers, ice makers. Custom solution, 1-year warranty.
2026-10-19
Guangzhou Lengtong Refrigeration Equipment Co., Ltd.——Company Promotion
LTZL is a refrigeration manufacturer located in Foshan with over 20 years of industry experience. We provide cold rooms and solar-powered cold storage solutions. Multiple compressor brands are available for selection. We offer remote technical support and full after-sales service.
2025-10-14
The Complete Cold Room Guide: Stable Temperature Storage for Food & Industrial Business
Custom cold rooms maintain constant temperatures to preserve food, medicine and logistics goods. This guide covers insulation, refrigeration matching, airflow layout, temperature monitoring and energy-saving tips, plus our exclusive nitrogen welding process to prevent pipe oxidation and refrigerant leaks. Contact us for customized cold storage solutions.
2026-06-10
Cold Room 2026 Complete Guide: Cost, Design, Maintenance & Efficiency Tips
This comprehensive 2026 guide breaks down core cold room definitions, real-world application scenarios, 2026 cost benchmarks, evidence-based design best practices, and long-term maintenance strategies. We draw on 15+ years of refrigeration manufacturing experience, peer-reviewed industry research, and field installation data to help commercial operators reduce energy waste, extend product shelf life, and meet global food safety standards.
2026-11-10
2026 Ultimate Guide: Choosing a Reliable Refrigeration Manufacturer in China
This comprehensive 2026 guide breaks down how global buyers can evaluate, vet, and partner with a qualified refrigeration manufacturer in China. It covers core industry standards, key vendor selection criteria, real-world performance data from active projects, common sourcing pitfalls to avoid, and transparent insights into China’s refrigeration manufacturing ecosystem. The content draws on 15+ years of practical supply chain experience from Lengtong Refrigeration (gdltzl.com) to help buyers reduce procurement risk, align equipment specs with project requirements, and build long-term, cost-effective supplier partnerships.
2026-10-27
2026 Complete Guide to Solar-Powered Cold Storage: Benefits, Costs & Custom Solutions
This comprehensive guide to solar-powered cold storage combines over 15 years of hands-on installation experience from Guangzhou Lengtong, a leading industrial refrigeration solutions provider. Backed by 2026 industry data, we cover core definitions, cost comparisons, planning steps, common misconceptions, and frequently asked questions to help you make an informed investment decision.
2026-09-14